![]() ![]() Initially, I installed PowerChute Business Edition, all three modules, but it could not find a UPS, despite Windows 7 installing drivers for a battery backup unit it found when I plugged the USB cable into the laptop.Īfter an hour of frustration, I rolled back the laptop to a prior restore point and downloaded PowerChute Personal Edition. I bought a special USB cable to do this, and put my Windows 7 laptop to the task. On a generator forum, I was told to download PowerChute and reprogram the thresholds for the UPS so it doesn't keep toggling AVR at the generator voltage. The relay switching is causing computers to reboot at random. Our SmartUPS 2200 is going into AVR frequently. Manufacturer won't do anything to correct it as it's within the 108-132 vac tolerance range they specify. We have a new genset and it's no load voltage is only 111 vac. ![]()